JSK0012

  • Case Material:ABS
  • Protection closs:IP20

  Enclosure Thermostat with two temperature seltings.
 
  Normally Open contact: commonly used in the monitoring filter fans, heat exchangers, or
when the temperature exceeds the set value, the closed circuit output signal.
 
  Normally Closed contact: commonly used in connecting the heater, when the temperature
reaches the set value, the broken line.

 

Technical data
Model JSK0012
Order 2021.010
Temperature range 0-60
Switching temperature tolerance 7K (± 4K)
Sensing element Bimetallic
Maximum switching capacity 10A / AC 230V
Electrical connection 4-pole 2.5mm, 0.8Nm
Installation 35mm DIN rail mounting
Terminal UL94Vo
Weight 90g
Size 69X50X46mm
Operating / storage areas -5 °C to +80 °C

Name download
JSK0012-1